Why shop local?
Local support
Local delivery service
Calibrated in our Dublin Lab
Warranty through us
Supports Irish Jobs
Megger MIT525 5kV Insulation Resistance Tester
Next day delivery on all orders placed before 2pm if in stock.
Megger MIT525 5kV Insulation Resistance Tester
The Megger MIT525 5kV Insulation Resistance Tester is an advanced 5kV test set for the diagnostic testing and maintenance of high voltage electrical equipment. In addition to measuring insulation resistance to 10TΩ, the MIT 525 also offers polarisation index, dielectric absorption ratio, step voltage, dielectric discharge and ramp testing.
In addition, the Megger MIT525 has advanced memory storage that allows test results to be logged complete with time/date stamping and simple recall of results to the screen. A fully isolated USB interface is used for the safe transfer of data to the supplied Megger PowerDB Lite management software package.
Simple operation is ensured with the two rotary switches while the large backlit display allows multiple results including resistance, voltage, leakage current, capacitance, battery level and test time to be displayed simultaneously.
Supplied in a rugged case that provides ultimate protection and a clip on lead pouch, the Megger MIT525 Insulation Tester is an extremely portable instrument with a CAT IV 600V safety rating in accordance with IEC 61010. A manufacturers calibration certificate is also supplied with the Megger MIT525.
Megger MIT 525 5kV Key Features:
- 10TΩ (5kV) max. insulation resistance
- Timed IR plus PI and DAR diagnostic tests
- Operate with dead battery when on line power/mains
- Rapid charge Li-ion battery – up to 6 hrs continuous testing (5kV)
- Dedicated voltmeter function (30V to 660V)
- Large LCD display with automatic backlight
- Noise filter – rejects up to 3mA noise
- Dielectric Discharge (DD), Step Voltage (SV) and ramp test functions
- Advanced memory with time/date stamp, on screen recall
- Download of memory via isolated USB (type B) interface (USB cable to PC)
- PowerDB Lite asset management software
Download Datasheet.
Which Megger HV MIT Digital Insulation Resistance Tester?
MIT515 | MIT525 | MIT1025 | MIT1525 | |
---|---|---|---|---|
Test Voltage | ||||
15.0 kV | ✔ | |||
10.0 kV | ✔ | ✔ | ||
5.0 kV | ✔ | ✔ | ✔ | ✔ |
2.5 kV | ✔ | ✔ | ✔ | ✔ |
1.0 kV | ✔ | ✔ | ✔ | ✔ |
500 V | ✔ | ✔ | ✔ | |
250 V | ✔ | ✔ | ||
Measurement | ||||
Max reading | 10 TΩ | 10 TΩ | 20 TΩ | 30 TΩ |
Min reading | 10 kΩ | 10 kΩ | 10 kΩ | 10 kΩ |
Voltage | ✔ | ✔ | ✔ | ✔ |
Capacitance | ✔ | ✔ | ✔ | ✔ |
Leakage current | ✔ | ✔ | ✔ | ✔ |
Test Types | ||||
Timed insulation resistance | ✔ | ✔ | ✔ | ✔ |
Polarisation index | ✔ | ✔ | ✔ | ✔ |
Dielectric absorption index | ✔ | ✔ | ✔ | ✔ |
Step voltage | ✔ | ✔ | ✔ | |
Dielectric discharge | ✔ | ✔ | ✔ | |
Ramp | ✔ | ✔ | ✔ | |
Other Feature | ||||
Analogue and digital display | ✔ | ✔ | ✔ | ✔ |
Short circuit current | 3 mA | 3 mA | 3 mA | 4 mA |
Rechargeable | ✔ | ✔ | ✔ | ✔ |
Timer control and display | ✔ | ✔ | ✔ | ✔ |
Max noise rejection | 3 mA | 3 mA | 3 mA | 4 mA |
USB output | ✔ | ✔ | ✔ | ✔ |
Software | ||||
PowerDB Lite | ✔ | ✔ | ✔ | ✔ |